ARMAC DevNotes · pages: Overview · Design & Calculations · Throttle Pressure-Drop Tables · Build & Commissioning · Calibration

Givens

SymbolMeaningValue
Q_mainThrottled delivery (sprinkler baseline)120 L/min = 7200 L/H = 2.000 L/s
Q_openDelivery wide open (tap out of circuit)~220 L/min
Pump10 HP High-Flow 3" setshut-off 530 kPa (5.3 bar); flat to ~400 L/min knee
P_highPump / high side at 120 L/min~5.1 bar
P_lowSprinkler / low side at 120 L/min~1.5 bar
DeltaP_tapDrop across the manual tap~3.6 bar
CTarget concentration0.014 (1.4%)
Q_sideBranch flow through injector~2000 L/H (needle-trimmed)
rDosatron dial~5% (range 1-10%)
DosatronHuiji DN00950-2500 L/H, 0.2-6 bar, 1-10%, G3/4"

1. Why full-flow injection is impossible

The injector passes at most 2500 L/H; the main is 7200 L/H -- 2.88x larger. So the whole main can never pass through it. Only a small branch is dosed and returned; the 120 L/min to the sprinklers is preserved.

2. Mass balance (governs everything)

Delivered concentration C = Q_gel / Q_total, where Q_total is the flow reaching the sprinklers during dosing. At the 120 L/min baseline:

Q_gel = C x Q_main = 0.014 x 7200 = 100.8 L/H = 1.68 L/min

During dosing the open branch adds flow, so Q_total rises to ~130-150 L/min and the true gel target is ~110-125 L/H. The exact figure is set by drum-drawdown calibration against the main flow sensor (see Build & Commissioning), not guessed.

3. Injector capacity -- one unit is ample

Q_gel,max = r_max x Q_side,max = 0.10 x 2500 = 250 L/H   ->  margin ~2-2.5x

4. Operating point

Run the branch at ~2000 L/H (needle-trimmed), dial ~5%:

r = Q_gel / Q_side ~= 100.8 / 2000 ~= 5%

Both sit mid-range in the 50-2500 L/H window and the 1-10% dial. Needle valve = flow trim; dial = concentration trim.

Sprinkler floor is structural. The branch is a parallel path around the tap, so opening it adds a second inflow to the low-side node, raising low-side pressure and therefore sprinkler flow (Q = K*sqrt(P)). During dosing:

Q_total in [120, 120 + Q_branch] ~= 130-150 L/min   ->  always >= 120

5. Pressure -- driven by the throttle (from the real curve)

The 3" curve is flat: shut-off 5.30 bar, h(120) ~= 5.1, h(220) ~= 4.9 bar. Anchor the sprinkler square law at wide open (sprinklers ~= pump head at 220 L/min):

P_low(120)  = 4.9 x (120/220)^2  ~= 1.5 bar
DeltaP_tap  = 5.1 - 1.5           ~= 3.6 bar   (~7x the injector's ~0.5 bar need)

Because the flow reduction is a field measurement, the full DeltaP and P_low lookup is tabulated over Qopen, Qdel = 100-300 L/min in Throttle Pressure-Drop Tables.

Pressure around the branch:

High tap        ~5.1 bar
- needle valve  sheds ~3.0 bar (surplus)     <- adjustable
Dosatron inlet  ~2.0 bar   in [0.2, 6] OK  (4 bar headroom)
- Dosatron loss ~0.5 bar
Dosatron outlet ~1.6 bar
- check valve   ~0.1 bar
Low tap         ~1.5 bar

The Dosatron inlet self-parks near 2 bar regardless of the exact DeltaP, so the design is insensitive to the precise throttle drop. The flat pump curve also means the branch's extra ~17-33 L/min draw barely shifts the operating point.

6. Pipe sizing

Branch ~= 2000 L/H = 33 L/min = 0.556 L/s -> 25 mm branch pipe (v ~= 1.13 m/s), reducing to G3/4" at the injector. The high-side leg must be rated for ~5.1 bar.


Page last modified on July 01, 2026, at 09:45 am