The boosterless design is driven by the pressure drop the manual throttle tap develops when it brings delivery down from wide-open flow to the throttled sprinkler flow. Because that flow reduction was originally a guesstimate, the tables below give the resulting drop across the tap (DeltaP) and the low-side pressure for every combination -- so once the two flows are measured, the real numbers are a lookup, not an estimate.

Model

Two well-established relations, no fitting beyond reading the pump curve:

  1. Pump head h(Q) -- digitised from the 10 HP High-Flow 3" curve. Shut-off 5.30 bar (530 kPa), essentially flat to the knee at ~400 L/min: h(120) ~= 5.08, h(220) ~= 4.92 bar.
  2. Sprinkler square law -- sprinklers are fixed orifices, so P_spr proportional to Q^2. Anchoring at the wide-open point (tap out of circuit, sprinklers see ~= pump head):
P_low  = h(Qopen) x (Qdel / Qopen)^2
DeltaP_tap = h(Qdel) - P_low

Qopen = wide-open (unthrottled) delivery; Qdel = throttled delivery to the sprinklers. Cells with Qdel > Qopen are non-physical (a throttle cannot raise flow) and are shown as middot.

Reading it for the branch: the Dosatron needs only ~0.5 bar of drop to run, so any cell with DeltaP >= 0.5 bar drives the branch -- essentially the whole physical region. The Dosatron inlet parks at roughly P_low + 0.5 bar, always well under its 6 bar ceiling. The design point (Qopen ~= 220, Qdel = 120) reads DeltaP ~= 3.6 bar, P_low ~= 1.5 bar.

Table 1 -- DeltaP across the tap (bar): the branch driving pressure

Rows = wide-open flow Qopen; columns = throttled delivery Qdel (both L/min).

Qopen \ Qdel100110120130140150160170180190200210220230240250260270280290300
1000.0····················
1100.90.0···················
1201.60.80.0··················
1302.11.50.80.0·················
1402.52.01.40.70.0················
1502.92.41.81.30.70.0···············
1603.12.72.21.71.20.60.0··············
1703.43.02.62.11.61.10.60.0·············
1803.63.22.82.52.01.61.10.60.0············
1903.73.43.12.72.31.91.51.00.50.0···········
2003.83.63.33.02.62.21.81.41.00.50.0··········
2104.03.73.53.22.92.52.21.81.40.90.50.0·········
2204.13.93.63.43.12.82.42.11.71.30.90.50.0········
2304.24.03.83.53.33.02.72.42.01.71.30.90.50.0·······
2404.34.13.93.63.43.22.92.62.32.01.61.30.90.40.0······
2504.34.24.03.83.63.33.12.82.52.21.91.61.20.80.40.0·····
2604.44.24.13.93.73.53.23.02.72.52.21.91.51.20.80.40.0····
2704.54.34.14.03.83.63.43.22.92.72.42.11.81.51.10.80.40.0···
2804.54.44.24.13.93.73.53.33.12.92.62.32.01.71.41.10.70.40.0··
2904.54.44.34.14.03.83.63.43.23.02.82.52.22.01.71.41.00.70.40.0·
3004.64.54.34.24.13.93.73.53.43.23.02.72.42.21.91.61.31.00.70.30.0

Table 2 -- Low-side pressure P_low (bar): Dosatron return pressure

Add ~0.5 bar for the Dosatron inlet pressure.

Qopen \ Qdel100110120130140150160170180190200210220230240250260270280290300
1005.1····················
1104.25.1···················
1203.54.35.1··················
1303.03.64.35.1·················
1402.63.13.74.45.1················
1502.22.73.23.84.45.0···············
1602.02.42.83.33.94.45.0··············
1701.72.12.52.93.43.94.55.0·············
1801.51.92.22.63.03.54.04.55.0············
1901.41.72.02.32.73.13.64.04.55.0···········
2001.21.51.82.12.42.83.23.64.14.55.0··········
2101.11.41.61.92.22.52.93.33.64.14.55.0·········
2201.01.21.51.72.02.32.62.93.33.74.14.54.9········
2300.91.11.31.61.82.12.42.73.03.33.74.14.54.9·······
2400.81.01.21.41.61.92.22.42.73.03.43.74.14.44.8······
2500.80.91.11.31.51.72.02.22.52.83.13.43.74.14.44.8·····
2600.70.91.01.21.41.61.82.02.32.52.83.13.43.74.14.44.8····
2700.60.80.91.11.31.51.71.92.12.32.62.93.13.43.74.14.44.7···
2800.60.70.91.01.21.31.51.71.92.22.42.62.93.23.43.74.04.44.7··
2900.60.70.80.91.11.21.41.61.82.02.22.42.72.93.23.53.74.04.34.6·
3000.50.60.70.91.01.21.31.51.71.82.02.32.52.73.03.23.53.74.04.34.6

How to use at the bench

  1. Wide open (bypass loop only, manual tap fully open), read the delivery flow -> Qopen.
  2. Throttle to your operating point, read the delivery flow -> Qdel.
  3. Look up the cell: DeltaP drives the Dosatron branch; P_low + 0.5 is the Dosatron inlet. Any DeltaP >= 0.5 confirms the boosterless design works.

Assumptions & caveats

  • Pump head read from the 3" curve by eye (+-~0.1-0.2 bar); the shut-off checks against the stated 530 kPa, so the digitisation is anchored.
  • High side taken at the delivery flow. If the high-pressure bypass raises total pump flow, the high side sits slightly lower per the (flat) curve, marginally reducing DeltaP -- negligible below the 400 L/min knee.
  • Sprinkler K assumed constant (fixed nozzle set, no zone changes between the two readings).
  • Elevation between tap points assumed small (< ~0.2 bar); add it in if the branch rises or drops more than ~2 m.