ARMAC uses two separate 13-core cables, plus some smaller ones. Confirm any core with a meter before reusing it.

Last checked: 7 November 2026.

1. House to pump shed (underground)

A 13-core Toro irrigation solenoid cable, 0.5 mm cores, about 10 m between the house and the shed. Only 4 of the 13 cores are used:

UseCoresNotes
RS-485 link, AR1 to AR3 (A and B)2 (pink and tan, per the old wiring notes)Gravity DFR0845 boards at each end; a 120 Ω terminating resistor is switched in on one board
Backup link, AR1 A4 to AR3 A21Plain 5 V serial, one direction
Backup link, AR3 A1 to AR1 A51Plain 5 V serial, the other direction
Spare9If the backup link proves unreliable over the cable, about 7 spare cores can be tied to the common ground bus at both ends (not to the Arduino GND pins), keeping one or two free

To record on site: the colours of the two backup-link cores, and whether a 300 Ω series resistor is fitted on each transmit line (AR1 A4, AR3 A1). TestSys, with its short wires, has none.

The shed and house share a common ground through the heavy power cable below, which is also earthed with a stake.

2. Module 3 (Relay) to Module 4 (Autonomous Control), in the shed

The blue multicore core allocation, as confirmed on site (it differs from the original colour plan and from the numbering on the Electronics System diagram).

CoreColourFunctionNotes
1PurplePump latch relay output to the R8 inputR8 drives SFS01 wire 1 through the isolation switch
2Light blueBackup link to the housePasses through Module 3
3BlueRelay R7 (recirculation valve)AR3 D4 (P1)
4OrangeRelay R5 (flow valve)AR3 D6 (P3)
5RedRelay R6 (shed cooling)AR3 D5 (P2)
6Dark greenRelay R4 (gel)AR3 D7 (P4)
7BrownBackup link to the housePasses through Module 3
8GreySpareNot connected at the house end
9WhiteTemperature sensor bus to AR2 D71-Wire, three DS18B20 sensors
10BlackWater pressure to AR2 D13From the optocoupler board
11YellowOil pressure to AR2 D10From the optocoupler board in Module 3
12PinkRS-485Underground link to AR1, passes through Module 3
13TanRS-485Underground link to AR1, passes through Module 3

3. Other cables

CableUse
House-to-shed power cableTwo-core, 10 AWG. Links the shed battery with the 10 A Victron charger in the house; all systems share the battery negative as common ground
3-core cable, Module 4 to the relay cabinetCore A: AR3 D8 to starter relay R1. Core B: AR3 D9 mode input (BOX/BYPASS). Third core: to record
Pump harness7-core YY cable (numbered cores) between the SFS01 controller and the pump