Pump shed key location is specified in the local instructions file.

  • When a bushfire threat is imminent, send the SMS mobileon to the RUT240 to turn on its mobile data, so that the Fritzbox can fail over to it if the NBN fails (and mobileoff when the threat has passed); top up the SIM credit if it is low (see Camera and apps)
  • Ensure the pump diesel fuel tank is full on departure
  • Check the pump oil level with the dipstick. Top up with 15-W40 engine oil.
  • Oil was changed after the first 20 hours of operation as specified in the engine manual. Engine uses approximately 2 L of fuel per hour, and has a 13 L tank. So one tank of fuel runs for 6.5 hrs, and oil change after 3 tanks of fuel used.
  • Oil change every 100 hours (15 tanks of fuel) or once a year, whichever comes first. Do the annual change before the fire season starts, and change the oil again after any long run during a fire. Oil ages even when the engine is little used, because moisture condenses in the crankcase and combustion acids remain in the oil.
  • Every month or two, run the engine long enough to reach full temperature (20-30 minutes) so that any moisture in the oil is driven off, and check that the oil on the dipstick is not milky (a sign of water).
  • Test run sprinklers at the beginning of the fire season checking that they sweep correctly through their full range of rotation and that their nozzles are not blocked.
  • Ensure no vegetation has grown up blocking or partially blocking the intended arc of spray.

Pump fuel cock in ON Position

In on position fuel cock lever is vertical down (labelled “O”). To stop move to horizontal position.

<< Current Fire Threats Calculations and Coding | | Troubleshooting >>      |Table of Contents>