The ARMAC fire defence system is usually operated from its Control Dashboard which can be accessed on any iphone, ipad or computer either from a web browser or from an app. You will be supplied with access details when you become an authorised user.''' The main page of that Dashboard is shown below.

Explanations of all controls, sensor outputs, and companion apps are also provided in the Help page accessed on the left sidebar of the Main Controls dashboard. But here is an explanation of each control:

  • Auto (Autonomous Mode): when turned ON puts the system into a “set and forget” mode where the system responds automatically to rising temperature, tank water levels, and battery voltage (ember detection raises an alert). Clicking OFF returns the system to manual control.
  • UNLOCK (Enable Controls): when Off (locked), the dashboard cannot turn on the pump, sprinklers, high flow or gel, and shed cooling can be stopped but not started - the lock can always stop water use, but never start it. Setting UNLOCK On allows all controls to be used. The lock also shows as on whenever Autonomous mode is active, but it does not stop Autonomous mode itself (see Output Control and Safety Interlocks).
  • HB (heartbeat): shows ON while the dashboard is in control (remote/manual operation). It goes OFF when Autonomous mode has taken over (see The Heartbeat System and Mode Transitions).
  • Pump (OFF) / ON: is a toggle to manually turn the pump ON or OFF.
  • Flow High/Reduced: reduces water flow to the sprinklers from approximately 217 L/min (maximum) to about 147 L/min (minimum required for operation).
  • Gel (OFF) / ON: is a toggle to manually turn the injection of fire-retardant gel into the sprinkler water ON or OFF (see The Gel Injection System).
  • Shed Cool Cycle: turns on sprinklers to cool the shed, utilising gravity feed water if the pump is not active.
    • Disable Shed Cooling: enables or disables shed cooling. Turning it ON disables shed cooling completely, including overriding the automatic pump-linked behaviour described below.
    • Time ON / Time OFF (set with the - and + buttons): sets the shed cooling intermittent cycle in minutes (0-30). If both are set to zero (and shed cooling is not disabled), shed cooling comes on automatically when the Pump comes on and turns off when the Pump turns off .
  • Sprinkler Cycle: activates intermittent spraying based on user-defined “on” and “off” sliders. The Recirc/Pump switch determines if “off” time uses water recirculation or shuts the pump down (subject to battery and time constraints).
  • ARMAC Alerts / Master Enable (on the SMS Alerts panel): is the master switch to enable system alerts. Specific alerts can be selected in the adjacent panel, and a test alert can be sent using the “Send Test Alert” button.
  • Pump Stop Retry: fires if the pump has not stopped 45 seconds after a stop command was sent and sensor readings still indicate the pump is running. AR1 automatically sends a second stop command at that point. This alert can be enabled or disabled independently via its switch in the alerts panel. (Note: at present this check cannot trigger; until it is corrected, check yourself that the pump has stopped.)

Sensors

The sensor outputs shown above help you monitor the system. Temperature sensors report the temperature inside and the shed battery and the water remaining in the tank are also shown.

Finally the pump’s oil and water pressure is shown OFF or HIGH. If HIGH then this confirms that the pump is actually running and pumping water. Ember detection shows CLEAR, or DETECTED if the ember detector sees a flame, which raises an alert. The Diesel Fuel Level gauge shows the diesel level in the tanks (at 0% about 6 litres still remain), the Sprinkler Pump Flow gauge and the Water panel show the water flow, and the Fire Cam gives a live camera view of the property.

Additional Panels

You will find some more information in panels provided in Home Assistant additional to the MAIN CONTROLS dashboard described above. As these are not essential and in general self-explanatory you can explore them at your leisure. The additional panels are:

  • SMS Alerts: provides a list of alerts (external temperature > 47 deg C; Pump started; Water level < 1 meter; Embers detected; No data from shed) which can be switched on to be sent as text messages to nominated phone numbers. The numbers must be entered into configuration.yaml in the Raspberry Pi. If internet connection is lost for more than 5 min, the system automatically switches to Autonomous mode (see below). Once the system regains internet contact, the system remains in Autonomous mode but sends an SMS message to let the users know that they can re-assert manual control if and when they wish.
  • Environment: provides details of the local weather – temperature, humidity, wind speed and direction, maximum expected temperature and weather forecast, along with a panel of warnings and incidents from the Victorian Government Emergency app.
  • Autonomous Mode State: shows whether Autonomous mode is on and why, what its sprinkler and shed cooling cycles are doing, and which of the main functions (pump, sprinklers, shed cool, reduced flow and retardant injection) are actually ON or OFF.
  • System Health: Here you will see a control which switches Autonomous Mode on and off. To the right are the Tuya Smart Switch controls which enable the Raspberry Pi (switch 1) and the Fritzbox router (switch 2) to be power cycled if trouble is encountered. Note that if the Raspberry Pi goes down for some reason it will be necessary to use the Tuya Smart app to restart it as the Home Assistant dashboard will become unavailable. In either case the RUT240's mobile data must first be turned on by SMS (mobileon), since the Tuya relay board is reached through the RUT240 (see Troubleshooting).
There is also an AR3 Comms Path Test switch. This is a technician's switch only used to test the two alternative communication paths available via different wire pairs in the underground cable between Pump Shed and House. Beside it, AR1 actually using shows the path setting AR1 itself is following (a forced setting ends by itself after 30 minutes), Data age shows how many seconds since AR1 last received data from the pump shed, and No data from shed warns when that passes 60 seconds. AR2 live shows whether AR2's readings are current; if not, the readings shown are the last ones received. For more on this see Communications
A Battery panel shows the battery as read by AR1, and the lowest voltage and length of the last dip (for example while the starter cranks). AR2's own battery reading is shown alongside, but it reads full scale until its divider is corrected.
Finally there is the AR1 Development Mode switch. This is also a technician's switch only used during development. When turned on it ensures that no states are retained on a reboot so the system returns as a "blank slate". If turned off certain states (pump, timing, valves) are stored in EEPROM memory and restored after a reboot.