Checks to run after loading new code at Fairhaven, or after any significant change.
Last updated: 7 November 2026.
Before loading
- Put the system in manual, with Enable Controls OFF (locked). Note the tank level, temperatures and battery.
- AR3: check the BOX/BYPASS mode input (D9) is as intended (BOX = open, at present) and the LATCH_FB_FITTED setting matches the wiring.
- No board has its TestSys strap fitted (AR1 A3, AR3 D11). After loading, each should report PRODUCTION.
- Temperature probes: warm each in your hand in turn and note which reading rises, so inside and outside are mapped correctly in AR2.
Loading
Load one board at a time - AR2, then AR3, then AR1 - and check each starts and reports to Home Assistant before the next. Load AR1 straight after AR3. If a board doesn't start after an upload, restart it with the upload script. To go back, reload the previous version of that board.
After loading: the Restarts card shows a cause for each board, and Connection self-restarts is ON.
Functional checks
- Valve directions (manual): run a sprinkler cycle. The sprinklers should spray in the ON phase and the water recirculate to the tank in the OFF phase; the Autonomous dashboard's Recirc valve row should agree.
- Flow and gel: high and reduced flow switch properly; turning gel on forces reduced flow.
- Sensors: Sensor status shows temperatures OK and tank level source "Gauge"; readings plausible.
- Pump from the dashboard: start and stop; oil and water pressure come up within a few seconds and drop after stopping. Until the stop-check fix is loaded, confirm the pump has really stopped.
- Hand-over: switch Autonomous Mode on - the 5-minute countdown should end with "AR3 in control (Auto)". Switch it off: control returns within about 20 s, with the pump and sprinklers off.
- Test button: hold 3 s; the dashboard switches to Autonomous by itself; watch the stages on the Autonomous Mode State dashboard. At Fairhaven, with real sensors, AR3 should end "watching, no trigger". Switch Autonomous off: back to manual with the pump off.
- Alerts: no temperature or tank-gauge alerts during the checks.
- Backup link over the real cable (about 1 hour): check the backup wiring (AR1 A4 → AR3 A2, AR3 A1 → AR1 A5) and note any series resistors; force BACKUP; run the pump for at least 10 minutes and toggle a valve; then set AUTO (back to RS-485 after 60 s). Pass: no bad messages from AR1 to AR3, under about 3% of AR3's messages rejected, no restarts or Auto takeovers, every command works. If it is worse, tie spare cable cores to ground at both ends first (see Multicore cables).
- Message rejection (optional): set FRAME_REJECT to 1 in AR1 and AR3, load AR1 then AR3, and repeat checks 4, 6 and 8.
- Afterwards: watch AR1's "last reset" for a few days; report any restart that isn't power or an upload.
Also check
- The Tuya relay board (Module 1): with the RUT240's mobile data turned on by SMS, it should appear in the Tuya app (it shows offline when mobile data is off, which is normal).
- The tank sensor's vent is clear.
- Leave the system as wanted for your absence: normally manual, locked, ready to switch to Autonomous remotely.