Status: designed, not yet built. The ember detector in use today is the infrared flame sensor described in Sensors; it raises an alert only.

Purpose

The aim is to detect airborne glowing embers arriving at the house early in an ember attack, before spot fires develop, using the industrial Pyrotector 30-2054 high-speed glowing-ember detector already held (see Sensors and its instruction manual), and to report each detection to the ARMAC AR1 controller.

The Pyrotector responds to infrared radiation between 1 and 3 microns, but it must work in light below 10 foot-candles (about 108 lux) - sunlight sets it off. So its housing has two jobs: to carry wind-borne embers past the detector from whatever direction the wind is blowing, and to keep daylight off its lens.

The design: a four-pipe pinwheel box


Figure 1. Plan view of the pinwheel box (click to enlarge)


An aluminium box (465 × 205 mm in plan, 270 mm deep) carries four 150 mm PVC stormwater pipes, one through each side wall. Each pipe passes straight through the wall and then, outside the box, turns through a standard 88° stormwater bend laid on its side, so that its mouth faces along the wall. The four mouths face four different directions, like a pinwheel.

Whichever mouth faces the wind receives nearly the full wind pressure, while the other three sit in suction and act as outlets. Air and embers therefore enter through the windward mouth, pass through the box and leave through the others - from any wind direction, and with no moving parts.

Inside the box the opposite stubs are in line, and the two pairs cross at the centre, directly beneath the detector mounted on the lid. So whichever pipe is the inlet, the main stream of air and embers passes under the lens, about 135 mm below it.


Figure 2. Section along the box, showing the detector and the ember path (click to enlarge)


The design has several advantages. There is no swivel, vane or slip ring to wear or stick. Each 88° bend leaves no straight line of sight into the box, so light can only get in by reflecting off the black inside of the bend. And it uses the existing box and standard stormwater bends, with few or no glued joints.

Other arrangements were considered and rejected. Straight pipes without bends would be simplest, but low sun shining straight along a pipe leaves only a small margin against the light limit. Elbows turned down inside the box will not fit - a 150 mm elbow is too big for the 205 mm width of the box - and a 45° elbow does not block the line of sight. PVC pipes are used since ember detection is required well before a fire front arrives and by the time the pipes are affected by heat the temperature rise itself will be the primary basis of decisions on system settings.

The trade-off. Embers do not follow the bend. Each strikes the outer wall of the bend once and is then carried on into the box by the airflow. Some break up, but the fragments still glow, and the larger embers that can ignite a house are the most likely to survive. In a real ember attack embers arrive in numbers, so losing a fraction at the bend does not prevent detection. A slight fall towards the box lets embers slowed at the bend roll inward. Long-sweep bends would be gentler on embers, but are much larger and dearer; standard bends are used for compactness and cost.

Where it goes

On the device. The detector sits centred on the lid, lens facing down, directly above the point where the four stubs cross. The lid needs a 28.6 mm (1-1/8 inch) lens hole, with two 6.35 mm (1/4 inch) bolt holes 88.9 mm (3-1/2 inch) apart, one either side. The detector body stays outside the box, and its full-face neoprene gasket must seal against a flat surface - if the lid is ribbed or embossed, a small flat aluminium plate is fitted under the detector and sealed to the lid. A sun and rain hood about 20 mm above the detector keeps its housing below its 65 °C rating in summer sun and keeps rain off the conduit entries. Lifting the lid gives access for inspecting and cleaning the lens (spiders, dust and soot).

On the site. The box goes on a post at about mid-height of the house - the zone that embers strike when they reach walls, eaves and nearby combustibles - and clear of walls, buildings and trees by at least the width of the device, so that all four mouths see the wind. It is turned so that the stubs lie on the diagonals and the mouths face NW, NE, SE and SW. The dangerous north-westerly and south-westerly winds then meet a mouth head-on, and the pipes are kept away from the bearings of the low sun in the fire season (roughly ESE at sunrise and WSW at sunset). It also needs to be within practical cable reach of AR1, and somewhere it can be reached safely for inspection.

The detector

The figures relied on, from the Pyrotector instruction manual (95-8363-01):

ParameterValue
Operating voltage12-16 V DC (12 V unit), 20-27 V DC (24 V unit)
Operating currentstandby 12 mA maximum, alarm 70 mA maximum
Relay outputdry Form C (SPDT), 1 A at 26 V DC
Spectral range1.0-3.0 microns, peak 2.5 microns
Response time8 ms average
Ember size and speed1/16 to 5/16 inch, 25 to 10,000 ft/min
Detection distance (1/4 inch ember)up to 24 inches (30-2054), up to 54 inches (30-2054A)
Cone of vision90°, 75% sensitivity at 45° off axis
Ambient lightbelow 10 foot-candles; sunlight and incandescent light cause false alarms
Temperature range-25 °C to +65 °C
Lead coloursred +V, black 0 V, white relay common, blue NC, orange NO

The ember path lies about 135 mm below the lens, well within the detection distance, and at that depth the detector's view is about 270 mm across, covering the crossing point of the four stubs. Embers slowed by the bend and the box are still well within the specified speed range: an ember crossing the view at 5 m/s is in sight for about 50 ms, against the 8 ms response time.

Keeping the light out

Because each bend blocks any direct line of sight into the box, daylight must reflect at least once off a black surface before it can get in. Rough estimates of the light reaching the lens:

SituationLight at the lensAgainst the 108 lux limit
Daylight, interior matte blackwell under 5 luxlarge margin
Low sun shining into a mouth, interior matte blackabout 1-3 luxlarge margin
Any bare aluminium or grey PVC insidemany times higherlikely to fail

Paint is essential. Bare aluminium reflects about 90% in the infrared. The aluminium gets an etch primer, then a flat black, carbon-based paint inside the box, under the lid, and inside every stub and bend. IR-reflective ("cool") black paints must be avoided. These figures are estimates, and the field test (below) decides; if stray light does prove a problem, a short black tube around the lens will narrow its view to the crossing point.

Construction


Figure 3. Pipe fixing: platform, spacers and saddle straps carry the pipes (click to enlarge)


The principle is that the thin aluminium box only locates the pipes and seals the holes. All the weight and wind load is carried by a platform under the box, so nothing is glued to the box and its walls carry no load.

The box. A snug 162-163 mm hole is cut in the centre of each side wall, centred at mid-height (about 135 mm) - with plywood clamped firmly behind the wall and a 160 mm holesaw cutting through both, or with a fine metal jigsaw blade and filed to the line. The lid is drilled for the detector, a few 6 mm drain holes are drilled in the floor away from the centre, and the inside and the underside of the lid are etch-primed and painted flat black.

The pipes. Four standard 150 mm 88° PVC stormwater bends (160 mm outside diameter pipe size) are used. Male-and-female (M-F) bends are preferred: if the spigot end is long enough to pass through the wall and project 10-20 mm inside, it goes straight through the hole and no separate stub, pipe or glue is needed (the spigot length is to be checked in the store). Otherwise female-and-female bends are used, each joined with PVC primer and solvent cement to a short stub of 150 mm stormwater pipe that passes through the wall. The bends are turned sideways to form the pinwheel, painted flat black inside, and given a slight fall towards the box, so that embers that slow at the bend roll inward and rain drains into the box and out through the floor drains. Stainless or aluminium bird mesh of 20-25 mm over each mouth keeps out birds and large leaves while passing embers.

Fixing. A flat platform on the post top - 9 mm compressed fibre-cement sheet or an aluminium angle frame, probably about 0.9 × 0.7 m (to be measured from the bends actually bought) - sits under the box and all four bends, and the box is bolted to it through the floor, clear of the drain holes. Spacer blocks under each bend, near the wall and at the mouth end, bring the pipe up to the hole height (about 55 mm) and are trimmed to give the fall towards the box. Stainless pipe saddles over each pipe, screwed through the spacers into the platform, carry all the weight and wind load. At the wall, MS polymer sealant (Sikaflex or similar) around each pipe seals out light and rain while staying flexible enough to take the different expansion of PVC and aluminium - there is no glue or clamp at the wall. The platform is fixed to the post with a galvanised post-top bracket or angle brackets.

Wiring


Figure 4. Two-wire signalling from the detector to AR1 (click to enlarge)


Only two wires run from the detector to AR1. When the detector sees an ember, its alarm relay switches a load resistor across its own supply, so the current it draws jumps; AR1 watches that current. At the detector the leads are connected as follows:

LeadFunctionConnect to
Red+V supply+V conductor
Black0 V0 V conductor
Whiterelay commonred (+V)
Orangerelay normally openload resistor, then black (0 V)
Bluerelay normally closednot used; insulate

The load resistor is 330 Ω 2 W for a 12 V unit or 680 Ω 2 W for a 24 V unit, and on alarm it adds about 35-48 mA to the supply current. The connections are made in a small weatherproof junction box beside the detector on the lid (or inside the detector housing if there is room), and the cable enters the detector through a 1/2 inch cable gland in one of its conduit entries and runs down the post to AR1. With no rotating joint, no slip ring or ride-through capacitor is needed.

At AR1 the detector is supplied from the ARMAC 12 V supply (through the 12-24 V boost converter board already held, set to 24 V, if it is a 24 V unit). The supply passes through the normally closed contact of a re-arm relay, so the detector stays powered even if the Arduino fails; energising the relay cuts the power to reset the detector. It then passes through an INA219 current sensor (VIN+ from the re-arm relay, VIN- to the +V conductor; VCC, GND, SDA and SCL to the Arduino), whose 26 V supply-side limit a 24 V unit run at 24 V respects. The 0 V conductor returns to the supply 0 V, common with AR1 ground. The Arduino pins are to be assigned in the AR1 sketch.

How it works

Wind enters the mouth facing it, turns through the bend and passes along the stub into the box, and the other three pipes carry the air out. Embers strike the bend once, are carried on by the airflow, and cross the box beneath the detector. A glowing ember in the detector's view is detected within about 8 ms: the detector's red LED lights and its alarm relay closes, connecting the load resistor across the supply, and its own current rises from standby to alarm. The detector is believed to latch in this state until its power is removed (to be confirmed on the bench).

Signalling and supervision. AR1 reads the INA219 continuously. Suggested thresholds, to be set from the values measured at commissioning:

StateSupply currentMeaning
Normalnear the measured standby (12 mA or less)armed, no ember
Alarmstandby plus at least 25 mA, held for 50 ms or moreember detected, detector latched
Open circuitbelow about 3 mAbroken wire or failed detector
Short or overloadabove about 150 mAwiring fault
Supply faultbus voltage outside the detector's rangesupply or converter problem

Re-arming. On an alarm, AR1 records the event (time and count) and publishes it to MQTT. After a short hold (say 5 seconds) it energises the re-arm relay for at least 1 second (the minimum to be confirmed on the bench), then releases it and ignores the current reading for about half a second while the detector powers up. The detector is then armed again, and the cycle repeats for each ember.

Persistent embers. Some embers will settle on the floor of the box and keep glowing in view, so the detector will re-trigger as soon as it is re-armed. If the alarm returns within about a second of re-arming on several successive cycles, AR1 flags "ember in box", counts it as one persistent event rather than many embers, and lengthens the re-arm interval (for example to 30 seconds) until the re-triggering stops.

Response. A single detection may be a stray spark or a false trigger, so AR1 acts on the ember rate - for example new embers per minute over a rolling window - combined with the fire-danger state and the other ARMAC sensors, to escalate from monitoring to wetting to full defence. The thresholds are to be set in the AR1 sketch.

Parts and cost

PartSpecificationSourceEstimate (A$)
Boxaluminium box, 465 × 205 × 270 mmalready held0
Bends4 × 150 mm 88° PVC stormwater bends, M-F preferredBunnings or plumbing supplier60-120
Stub pipe and cementonly if F-F bends are used: short length of 150 mm stormwater pipe, primer and cementBunnings or plumbing supplier0 (M-F) or 50-80 (F-F)
Paintetch primer and flat black (carbon-based)hardware store40
SealantMS polymer (Sikaflex or similar), 1 cartridgehardware store15
Bird meshstainless or aluminium, 20-25 mmhardware store15
Platform9 mm compressed fibre-cement sheet (about 0.9 × 0.7 m) or aluminium angle framehardware store or building supplier30-50
Spacershardwood blocks, about 55 mmoffcuts0-10
Saddle straps8 saddles for 160 mm pipe, stainless or galvanisedplumbing supplier20-60
Post bracket and fastenersgalvanised post-top bracket, stainless bolts and screwshardware store30
Junction box and cable glandsmall IP65 box, 1/2 inch glandelectrical supplier15
Current sensorINA219 breakout moduleCore Electronics or AliExpress10
Re-arm relay5 V relay module (NC contact used)Core Electronics or AliExpress5
Load resistor330 Ω 2 W (12 V) or 680 Ω 2 W (24 V)electronics supplier1
Cable2-core outdooralready held0
Boost converter12-24 V, only needed if the detector is a 24 V unitalready held0
Totalabout 240-360 (M-F), 290-440 (F-F)

All prices are estimates. The bends are the largest item, and M-F bends avoid the stub pipe and cement altogether; any suitable bends, sheet or offcuts already held reduce the total.

Maintenance

Before each fire season: open the lid, clear leaves and debris, check the mesh, clean the lens and check that the drain holes are clear; look for spiders and wasps in the pipes and box; check the sealant at the wall holes and the saddle straps; and run the soldering-iron test (below) to confirm detection and reporting at AR1.

Commissioning

  1. Latching (on the bench, before assembly): power the detector, pass a 40 W soldering iron or a lit cigarette quickly across the lens, remove it, and confirm that the LED and relay stay on until the power is removed. Also find the minimum power-off time that resets it. If it does not latch, the sensing must capture brief pulses (a hardware interrupt or comparator) rather than polling.
  2. Currents: record the standby and alarm currents with the load resistor fitted, and set the AR1 thresholds from them.
  3. Sensitivity in place: with the device assembled, pass the soldering iron through the crossing point and confirm detection and reporting at AR1.
  4. Airflow: using a leaf blower as the wind, at the mouths and at 45° between them, hold a smoking incense stick at each mouth and confirm that air flows in at the windward mouth and out of the others.
  5. Embers: with the blower running, feed sparkler sparks or smouldering charcoal fragments into the windward mouth; confirm detection, and note where embers settle.
  6. Daylight: with the device in its final position and orientation, log detector triggers at AR1 over several sunny days, including sunrise and sunset. There should be none.
  7. Persistence: leave a glowing fragment on the floor, and confirm that AR1 flags it as a persistent ember rather than counting repeated embers.
  8. Rain: hose the device down; confirm that water drains out, the lens stays dry and no leakage current appears.
  9. Supervision: disconnect one conductor and confirm that AR1 reports an open-circuit fault.

Still to be settled

  • Confirm the latching behaviour and minimum reset time on the bench (believed to latch).
  • Confirm from its label whether the detector is the 12 V or the 24 V unit.
  • Check the lid is flat enough for the detector gasket, and add a flat plate if not.
  • Obtain the bends (M-F if the spigot is long enough), measure them, then set the platform size and spacer heights.
  • Assign the Arduino pins and write the INA219 sensing, re-arm and persistent-ember code for AR1.
  • Choose the post position on site.

Earlier designs for the housing - a vane-mounted duct on a swivel, a version with long-sweep bends, and a two-box windcatcher with an internal funnel - are described in Development history: sensors.

<< Sensors | | The Electronic Control Sub-System >>      |Table of Contents>


Page last modified on November 08, 2026, at 07:11 AM